Item | Dimensions | Number | Filter surface area | Volume flow rate | Initial pressure drop | Energy class / |
5-360/M5-3P | 287x287x360 | 3 | 0.6 | 650 | 53 | - |
10-360/M5-3P | 287x592x360 | 3 | 1.3 | 1400 | 53 | - |
40-360/M5-5P | 490x592x360 | 5 | 2.1 | 2300 | 53 | - |
47-360/M5-6P | 592x490x360 | 6 | 2.1 | 2300 | 53 | - |
48-360/M5-6P | 592x287x360 | 6 | 1.2 | 1300 | 53 | - |
50-360/M5-6P | 592x592x360 | 6 | 2.6 | 2800 | 53 | - |
60-360/M5-6P | 592x892x360 | 6 | 3.9 | 4200 | 53 | - |
Item | Dimensions | Number | Filter surface area | Volume flow rate | Initial pressure drop | Energy class / |
5-500/M5-4P | 287x287x500 | 4 | 1.2 | 850 | 65 | D |
10-500/M5-4P | 287x592x500 | 4 | 2.4 | 1700 | 65 | D |
40-500/M5-6P | 490x592x500 | 6 | 3.6 | 2600 | 65 | D |
47-500/M5-8P | 592x490x500 | 8 | 3.9 | 2800 | 65 | D |
48-500/M5-8P | 592x287x500 | 8 | 2.3 | 1700 | 65 | D |
50-500/M5-8P | 592x592x500 | 8 | 4.7 | 3400 | 65 | D / 945 kWh |
60-500/M5-8P | 592x892x500 | 8 | 7.1 | 5200 | 65 | D |
Item | Dimensions | Number | Filter surface area | Volume flow rate | Initial pressure drop | Energy class / |
5-600/M5-4P | 287x287x600 | 4 | 1.4 | 850 | 55 | C |
10-600/M5-4P | 287x592x600 | 4 | 2.8 | 1700 | 55 | C |
40-600/M5-6P | 490x592x600 | 6 | 4.3 | 2600 | 55 | C |
47-600/M5-8P | 592x490x600 | 8 | 4.7 | 2800 | 55 | C |
48-600/M5-8P | 592x287x600 | 8 | 2.8 | 1700 | 55 | C |
50-600/M5-8P | 592x592x600 | 8 | 5.7 | 3400 | 55 | C / 743 kWh |
60-600/M5-8P | 592x892x600 | 8 | 8.6 | 5100 | 55 | C |
All specifications refer to our standard product range. Due to constant technical developments, this information may change at any time without notice.
You cannot find what you are looking for? Do not hesitate to contact us.
Do you have any questions regarding our products or would you like a personal advice? No problem, contact us directly.
We'll be pleased to help you!